Tender Republic Ausschreibungen

Qualification system for grounding transformers

Netze BW GmbH, Stuttgart

Frist (abgelaufen)
keine Frist angegeben
Geschätzter Wert
nicht angegeben
Verfahren
Lieferung
Veröffentlicht
Laufzeit
28.04.2026 bis 31.12.2032
Für KMU geeignet
keine Angabe des Auftraggebers
CPV
31171000 Transformatoren mit Flüssigkeitsisolation

Beschreibung

The present qualification system serves as the prequalification for the supply of grounding transformers for the medium‑voltage network (10-30 kV). It ensures that all potential suppliers comply with the technical requirements of our specification as well as the commercial and procedural criteria necessary for approved supplier status.

4 Lose

  1. Los 1
    Grounding transformer with 10kV and 350A

    Lot 1 - NEB 10 kV / 350 A This lot covers a Grounding Transformer (NEB) with the following main characteristics: Vector group ZNyn5(d), cooling type ONAN, designed for short-term operation of 2 hours. The rated high-voltage level is 10.4 kV with a rated current of 350 A. The rated low-voltage level is 0.4 kV with a rated power of 400 kVA. The specified zero-sequence impedance is 3.5 Ω per phase. …

  2. Los 2
    Grounding transformer with 20kV and 800A

    Lot 2 - NEB 20 kV / 800 A This lot covers a Grounding Transformer (NEB) with the following main characteristics: Vector group ZNyn5(d), cooling type ONAN, designed for short-term operation of 2 hours. The rated high-voltage level is 21 kV with a rated current of 800 A. The rated low-voltage level is 0.4 kV with a rated power of 400 kVA. The specified zero-sequence impedance is 3.5 Ω per phase. …

  3. Los 3
    Grounding transformer with 20kV and 433A

    Lot 3 - NEB 20 kV / 433 A This lot covers a Grounding Transformer (NEB) with the following main characteristics: Vector group ZNyn5(d), cooling type ONAN, designed for short-term operation of 2 hours. The rated high-voltage level is 21 kV with a rated current of 433 A. The rated low-voltage level is 0.4 kV with a rated power of 400 kVA. The specified zero-sequence impedance is 3.5 Ω per phase. …

  4. Los 4
    Grounding transformer with 30kV and 280A

    Lot 4 - NPB 30 kV / 280 A This lot covers a Grounding Transformer (NPB) with the following main characteristics: Vector group ZN, cooling type ONAN, designed for short-term operation of 2 hours. The rated high-voltage level is 31,5 kV with a rated current of 280 A. The specified zero-sequence impedance is 10.5 Ω per phase. All applicable requirements shall comply with DIN IEC 60076.

Ähnliche offene Verfahren

Elektrotechnik in Deutschland, nach Frist sortiert. Alle anzeigen

  1. heute, in 3 Stunden
  2. heute, in 3 Stunden
  3. morgen
  4. morgen
  5. morgen
  6. morgen